- Home
- Cables by Application
- Fire Survival Cables
FIre Survival Cable

- Home
- Cables by Application
- Fire Survival Cables
Fire Survival (FS) Cables are specialized electrical cables designed to maintain circuit integrity during fire incidents, ensuring uninterrupted operation of critical systems when it matters the most. Unlike standard cables, FS Cables continue to function even in the presence of flames, helping support emergency lighting, alarms, ventilation, and safety equipment.
Engineered to prevent flame propagation and produce very low smoke, low toxicity, and minimal corrosive gases, these cables significantly improve visibility and reduce health risks during evacuation—making them ideal for tunnels, high-rise buildings, hospitals, metros, and industrial facilities. With fire-related hazards being a major cause of life and property loss, FS Cables play a vital role in enhancing safety and protecting essential infrastructure."
Certifications

Torrent Electricals Ltd. ISO45001

Torrent Electricals Ltd. ISO14001

Torrent Electricals Ltd. ISO9001
Standards

BS 7846
IS 17505 (Part 1)
BS 6387
IEC 60332 -1 & 3
IEC : 60331-1
Cable Construction Overview

Applications

Commercial & Residential
High-Rise Buildings, Shopping Malls & Entertainment Centers, Residential Complexes & Smart Homes, Banks & Financial Institutions

Energy & Utilities
Power Plants & Substations, Oil & Gas Refineries & Chemical Plants, Agricultural Storage & Processing Units

Industrial & Manufacturing
Industrial & Manufacturing Units, Mines & Underground Facilities, Defense & Military Installations

Infrastructure & Transportation
Metro Rail, Airports & Tunnels, Ports, Shipyards & Offshore Platforms, Heritage Buildings & Museums

Healthcare & Education
Hospitals & Healthcare Facilities, Educational Institutions & Universities, Pharmaceutical & Biotech Industries

Technology & Data
Data Centers & IT Infrastructure, Telecommunication & Broadcast Centers
| Parameter | Specification |
|---|---|
| Voltage Rating | 0.6 / 1.0 kV (or) 1.1 kV |
| Operating Temperature | -15°C to +90°C |
| Short Circuit Temperature | 250°C |
| Minimum Bending Radius | 12 × Overall Diameter |
| Test Voltage | 3500V AC at (20 ± 5)°C |
| Standards Followed | BS 7846:2016 & IS 17505:2021 |
| Core Identification as per BS 7846 | 2 Core: Brown, Blue 3 Core: Brown, Black, Grey 4 Core: Blue, Brown, Black, Grey 5 Core: Green-Yellow, Blue, Brown, Black, Grey Above 5 Core: Supplied with number printing (All cores optional number printing) |